Kyoritsu Indonesia - AC/DC Digital Clamp Meters KEW 2003A ,2004 ,KEW 2009R ,2010


Kyoritsu Indonesia : Multimeters,Voltage Tester,Clamp Meters,Insulation Testers, Earth Testers,Loop/PSC/RSD Testers,Loggers,Multi Function Testers,Portable Appliance Testers,Power Meters,Others, Sensors


 

AC/DC Digital Clamp Meters

KEW 2003A
 
Selection Guide Product Catalogue Instruction Manual
 

Equipped to measure both AC and DC current with transformer jaws of large diameter.
Can measure AC and DC currents up to 2000A.
Output terminal for connection to recorders.

Ø55 MAX AC/DC2000A ACV DCV
Ω Continuity OUT PUT MAX HOLD
2003A
CE
 
AC A 400A/2000A (0~1000A)
|±1.5%rdg±2dgt [50/60Hz]
|±3%rdg±4dgt [40~500Hz]
|±5%rdg±4dgt [500Hz~1kHz]
2000A (1001~2000A)
|±3%rdg±2dgt [50/60Hz]
AC V 400/750V
|±1.5%rdg±2dgt [50/60Hz]
|±1.5%rdg±4dgt [40Hz~1kHz]
DC A 400/2000A ±1.5%rdg±2dgt
DC V 400/1000V ±1%rdg±2dgt
Ω 400/4000Ω|±1.5%rdg±2dgt
Continuity buzzer buzzer sounds below 50±35Ω
Output
Recorder : DC400mV against AC/DC400A
  DC200mV against AC/DC2000A
Conductor Size Ø55mm max.
Safety Standard IEC 61010-1 CAT.IV 600V CAT.III 1000V
IEC 61010-031
IEC 61010-2-032
Frequency Response 40Hz~1kHz
Withstand Voltage 6880V AC for 5 seconds
Power Source R6P (AA) (1.5V) ×2
Dimensions 250(L) × 105(W) × 49(D)mm
Weight 530g approx.
Accessories 7107A (Test leads)
8201 (Output Plug)
9094 (Carrying Case)
R6P (AA) × 2
Instruction Manual
Optional 8008 (Multi-Tran) (AC only)
7014
(Output cord)

 


 

AC/DC Digital Clamp Meters

MODEL 2004
 
Selection Guide Instruction Manual
 

Smallest clamp meter capable of AC and DC current measurements.
20A range has a minimum resolution of 0.01A AC/DC.
AC/DC voltage and resistance measurement functions also available.

Ø19 MAX AC/DC200A ACV DCV
Ω      
2004
 
AC A 20/200A
|±1%rdg±2dgt [50/60Hz] (20A)
|±1.5%rdg±4dgt [40Hz~1kHz] (20A)
|±1.5%rdg±4dgt [50/60Hz] (0~150A)
|±2%rdg±5dgt [40Hz~1kHz] (0~150A)
|±3.5%rdg [40Hz~1kHz] (>150A)
AC V 500V
|±1.5%rdg±2dgt [50/60Hz]
|±2%rdg±4dgt [40Hz~1kHz]
DC A 20/200A
|±1%rdg±2dgt (20A)
|±1.5%rdg±2dgt (0~150A)
|±3%rdg (>150A)
DC V 200V ±1%rdg±2dgt
Ω 200Ω|±1.5%rdg±2dgt
Conductor Size Ø19mm max.
Frequency Response DC, 40Hz ~ 1kHz
Withstand Voltage 1000V AC for 1 minute
Power Source R6P (AA) (1.5V) × 2
Dimensions 180(L) × 54(W) × 32(D)mm
Weight 170g approx.
Accessories 7066A (Test leads)
9055 (Carrying case)
R6P (AA) × 2
Instruction Manual
Optional 8008 (Multi-Tran) (AC only)

 


 

AC/DC Digital Clamp Meter

KEW 2009R
 
Selection Guide Product Catalogue Instruction Manual
 

CAT.IV Clamp Meter can measure the Voltage and Current in both very low and high power circuits.
Accurate True-RMS reading of AC current or voltage with distorted waveform.
Can measure AC and DC currents up to 2000A.
NEW TRUE RMS CAT.IV 600V IEC61010
Ø55 MAX AC/DC2000A ACV DCV
Ω Hz Continuity OUT PUT
PEAK 10ms      
2009R
CE
 
AC A
400.0/2000A
±1.3%rdg±3dgt (0~400.0A, 150~1700A) (45~66Hz)
  ±2.0%rdg±5dgt (0~400.0A, 150~1700A) (20Hz~1kHz)
  ±2.3%rdg±3dgt (1701~2000A) (45~66Hz)
DC A 400.0/2000A±1.3%rdg±2dgt
AC V
40.00/400.0/750V
±1.0%rdg±3dgt (45~66Hz)
  ±1.5%rdg±5dgt (20Hz~1kHz)
DC V 40.00/400.0/1000V±1.0%rdg±2dgt
Ω 400.0/4000Ω|±1.5%rdg±2dgt
(Electronic protection (no fuse) up to 600V)
Continuity buzzer Buzzer sounds below 20Ω
Hz 10.0 ~ 4000Hz±1.5%rdg±5dgt
(Input sensitivityCurrent: more than 40AVoltage: more than 10V)
Output
Recorder : DC400mV against AC/DC400.0A
  DC200mV against AC/DC2000A
Withstand voltage 6880V AC for 5 seconds
Conductor size Ø55mm max.
Applicable standards IEC 61010-1 CAT.IV 600V, CAT.III 1000V Pollution degree 2
IEC 61010-031, IEC 61010-2-032, IEC 61326-1, IEC 61326-2-1
Power Source R6P (1.5V) × 2
Dimensions 250(L) × 105(W) × 49(D)mm
Weight Approx. 540g (including batteries)
Accessories 7107A (Test leads), 8201 (Output plug), 9094 (Carrying case)
R6P (AA) (1.5V) × 2, Instruction Manual
Optional 8008 (Multi-Tran) (AC only), 7014 (Output cord)

 


 

AC/DC Digital Clamp Meters

MODEL 2010
 
Selection Guide Instruction Manual
 

High sensitivity, miniature AC/DC clamp meter.
0.1mA minimum resolution for AC current and 1mA minimum resolution for DC current.
Output terminal for recorder connection.

Ø7.5 MAX AC/DC20A OUT PUT  
External Power Supply    
2010
Never make current measurement on a circuit above 60V AC/DC
as the instrument is designed for use on low voltage circuits only.
 
AC A 200mA/2/20A
|±1%rdg±2dgt [50/60Hz] (200mA)
|±1.5%rdg±4dgt [40Hz~2kHz] (200mA)
|±1%rdg±2dgt [50/60Hz] (2A)
|±2.5%rdg±5dgt [40Hz~2kHz] (2/20A)
DC A 2/20A
|±1%rdg±2dgt (2A)
|±1.5%rdg±4dgt (20A)
Output
Recorder : DC200mV against AC200mA/2/20A
  DC200mV against DC2/20A
Conductor Size Ø7.5mm max.
Frequency Response DC, 40Hz~2kHz
Withstand Voltage 750V AC for 1 minute
Power Source 6LF22(9V) × 1 or AC Adaptor
Dimensions 142(L) × 64(W) × 26(D)mm
153(L) × 23(W) × 18(D)mm
Clamp Sensor
Weight 220g approx.
Accessories 9071 (Carrying Case)
Alkaline 6LF22 × 1
Instruction Manual
Optional 8022 (AC Adaptor) (110V)
8023
(AC Adaptor) (220V)
7014 (Output cord)

 


 

Quick Contact






603878
Today
Yesterday
This Week
Last Week
This Month
Last Month
All days
94
462
1521
599255
7916
12693
603878

Your IP: 54.162.181.75
Server Time: 2017-09-21 10:38:52
You are here:   HomeKyoritsuClamp MetersAC/DC Digital 2003A,2004,2009R,2010

VISIT US

  • Plaza Kenari Mas , Lt. LG Blok B121 , Jalan Kramat Raya No. 101 , Paseban , Senen , Jakarta Pusat 10440 , Phone : 021-29478925
  • Kota Wisata Cibubur , Ruko Concordia SRB26 , Jalan Alternatif Cibubur , Bogor 16920 , Phone : 021-29478974
Kyoritsu Indonesia by PT. Best Instrument Indonesia | Ruko Concordia SRB 26, Kota Wisata Cibubur, Cileungsi, Bogor - Indonesia.